[1]WEI Xin-li,WANG Zhong-hua,GENG Li-hong,et al.Study on the Throttling Losses in CRS and Solutions[J].Journal of Zhengzhou University (Engineering Science),2015,36(03):68-72.[doi:10.3969/ j. issn.1671 -6833.2015.03.015]
Copy
Journal of Zhengzhou University (Engineering Science)[ISSN
1671-6833/CN
41-1339/T] Volume:
36
Number of periods:
2015 03
Page number:
68-72
Column:
Public date:
2015-06-30
- Title:
-
Study on the Throttling Losses in CRS and Solutions
- Author(s):
-
WEI Xin-li; WANG Zhong-hua; GENG Li-hong; MENG Xiang-rui
-
School of Chemical Engineering and Energy,Zhengzhou University,Zhengzhou 450001,China
-
- Keywords:
-
compression refrigeration; throttling loss; energy saving; ejector
- CLC:
-
TB61 +5
- DOI:
-
10.3969/ j. issn.1671 -6833.2015.03.015
- Abstract:
-
A thermodynamic model is established to make a theoretical analysis on conventional compressionrefrigeration systems ( CRS ),throttling losses under various operating conditions are simulated with MatlabR2010a.R134a is chosen as refrigerant in the model and its thermo-physical properties are obtained fromREFPROP 9.0.The results show that:1. throttling losses in CRS accounts for 13 to 31.9 of compressor pow-er; 2.throttling losses of double temperature CRS are about 50% higher than that of the single temperatureCRS; 3.throtling losses change with operating conditions. According to the characteristics of CRS, three com-monly used ways to recover throttling losses are analyzed. COP of C/ERS is simulated under various operatingconditions and compared with the simply recover throttling losses scheme,the results verify the feasibility of u-sing ejector in CRS.