[1]陈根永,高翔宇,谭 超,等.集中式馈线自动化配电网供电可靠性评估[J].郑州大学学报(工学版),2024,45(01):114-121.[doi:10.13705/j.issn.1671-6833.2023.04.006]
 CHEN Genyong,GAO Xiangyu,TAN Chao,et al.Evaluation of Power Supply Reliability of Centralized Feeder Automation Distribution Network[J].Journal of Zhengzhou University (Engineering Science),2024,45(01):114-121.[doi:10.13705/j.issn.1671-6833.2023.04.006]
点击复制

集中式馈线自动化配电网供电可靠性评估()
分享到:

《郑州大学学报(工学版)》[ISSN:1671-6833/CN:41-1339/T]

卷:
45
期数:
2024年01期
页码:
114-121
栏目:
出版日期:
2024-01-19

文章信息/Info

Title:
Evaluation of Power Supply Reliability of Centralized Feeder Automation Distribution Network
作者:
陈根永 高翔宇 谭 超 范旭光
1. 郑州大学 电气与信息工程学院,河南 郑州 450001; 2. 国网河南省电力公司新乡供电公司,河南 新乡 453000; 3. 国网河南省电力公司宝丰县供电公司,河南 平顶山 467400
Author(s):
CHEN Genyong 1 GAO Xiangyu 1 TAN Chao 2 FAN Xuguang
1. School of Electrical and Information Engineering, Zhengzhou University, Zhengzhou 450001, China; 
2. Xinxiang Power Supply Company of State Grid Henan Electric Power Company, Xinxiang 453000, China;
3. Baofeng Power Supply Company of State Grid Henan Electric Power Company, Pingdingshan 467400, China
关键词:
集中式馈线自动化 配电网 供电可靠性 预安排检修 负荷转供
Keywords:
centralized feeder automation distribution network power supply reliability pre-arranged maintenance load transfer
DOI:
10.13705/j.issn.1671-6833.2023.04.006
文献标志码:
A
摘要:
计及集中式馈线自动化的配电网可靠性评估尚存在较多研究空白,且多数研究仅计及故障停电的影响, 在考虑预安排检修容量约束的情况下,计及负荷转供影响,结合馈线自动化的类型及运行逻辑,依据馈线自动化相 关技术指标,对恢复供电过程中出现的负荷点进行详细分类,推导出不同类型负荷期望恢复供电时间和配电网供 电可靠性指标计算公式。 结合算例进行分析可知,不同终端配置 下 馈 线 系 统 平 均 停 电 持 续 时 间 SAIDI 可 减 少 0. 95 ~ 1. 08 h / (用户·a) ,说明了优化终端配置可有效提高配电网供电可靠性,证明了所提评估方法的准确性和实 用性,并比较了不同终端配置对可靠性的影响。
Abstract:
There were still some research gaps in reliability evaluation of distribution network considering centralized feeder automation, and most studies only focused on the impact of power failure. Considering the pre-arranged maintenance and capacity constraints, the influence of load transfer, and combined with the type and operation logic of feeder automation, according to the related technical indexes of feeder automation, the load nodes appearing in the process of power restoration were classified in detail. And the calculation formulas of expected power restoration time and power supply reliability indexes of different types of loads were derived. Combined with an example, the average outage duration SAIDI of feeder system was reduced by 0. 95-1. 08 h / ( user·a) with different terminal configurations in the example, which showed that optimized the terminal configuration could effectively improve the power supply reliability of distribution network, which proved the accuracy and practicability of the evaluation method in this study. The influences of different terminal configurations on reliability were compared.

相似文献/References:

[1]陈根永,侯永将,杨凤民,等.20kV配电电压等级的接地方式研究[J].郑州大学学报(工学版),2010,31(03):33.[doi:10.3969/j.issn.1671-6833.2010.03.009]
 CHEN Genyong,General Hou Yong,Yang Fengmin,et al.Research on grounding method of 20kV distribution voltage level[J].Journal of Zhengzhou University (Engineering Science),2010,31(01):33.[doi:10.3969/j.issn.1671-6833.2010.03.009]
[2]陈根永,孙栗,彭勇,等.基于层次分析法的郑州新区电压等级序列优化研究[J].郑州大学学报(工学版),2011,32(06):121.[doi:10.3969/j.issn.1671-6833.2011.06.029]
[3]王金凤,包毅,程跃森,等.城市配电网电容电流补偿研究[J].郑州大学学报(工学版),2012,33(04):69.[doi:10.3969/j.issn.1671-6833.2012.04.016]
[4]章健,王君亮,袁义江..基于GSM的配变电量自动采集系统的设计与实现[J].郑州大学学报(工学版),2004,25(02):63.[doi:10.3969/j.issn.1671-6833.2004.02.015]
 ZHANG Jian,Wang Junliang,Yuan Yijiang.Design and implementation of automatic power distribution and substation collection system based on GSM[J].Journal of Zhengzhou University (Engineering Science),2004,25(01):63.[doi:10.3969/j.issn.1671-6833.2004.02.015]

更新日期/Last Update: 2024-01-25